Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) NEW 200 AMP METER BASE FEED AN EXISTING INDOOR RATED DISCONNECT SWITCH. 2) GUTTER MUST BE RATED FOR OUTDOOR USE. 3) GROUNDING ELECTRODE CONDUCTOR SPLICES MUST BE PERMANANT TYPE PER ART 250 NEC. 4) LOAD CENTER TO RIGHT OF DISCONNECT MUST BE OUTDOOR RATED. CAN SEE DAYLIGHT AT TOP FROM INSIDE. 5) EXPOSED WIRING OUTSIDE. 6) THIS SERVICE AND ASSOCIATED WIRING, EQUIPMENT MUST BE BROUGHT UP TO CODE PRIOR TO POWER RELEASE. UNSAFE AS IS. 7) WORK TO BE DONE BY L-11 LICENSED CONTRACTOR. |