Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
9231 E OLD SPANISH TR
Apply Date:
06/24/2003
Applicant:
HOSANNA ELECTRIC *C
Description:
REPLACE:2 PANELS (APA)
Contractors:
  • HOSANNA ELECTRIC *C

Outstanding Activity Conditions

Permit Number - T03EL01243
Permit Status: Expired
Permit Description: REPLACE:2 PANELS (APA)
Total Outstanding Activity Conditions - 1
Date Name
06/24/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03EL01243
Permite Description: REPLACE:2 PANELS (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/30/2003 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*/ 1) CONDUIT USED TO CONCEAL/PROTECT GROUND WIRE REQUIRES A GROUNDING BUSHING AND BONDING JUMPER AT BOTH ENDS 2) A GROUNDING AND BONDING JUMPER IS REQUIRED AT BOTH ENDS OF OFF SET NIPPLE 3) ASSUME THIS OTHER PROJECT PREVIOUSLY PERMITTED AND APPROVED