Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/30/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CONDUIT USED TO CONCEAL/PROTECT GROUND WIRE REQUIRES A GROUNDING BUSHING AND BONDING JUMPER AT BOTH ENDS 2) A GROUNDING AND BONDING JUMPER IS REQUIRED AT BOTH ENDS OF OFF SET NIPPLE 3) ASSUME THIS OTHER PROJECT PREVIOUSLY PERMITTED AND APPROVED |