Permit: T03EL01233
Permit Details
Apply Date:
06/24/2003
Applicant:
ABUL AANAJAR
Description:
ELECTRIC:UPGRADE 200AMPS
Permit Reviews
Permit Number - T03EL01233
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE 200AMPS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/24/2003 | ELECTRICAL | 06/24/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL01233
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/24/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03EL01233
Permite Description: ELECTRIC:UPGRADE 200AMPS
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2003 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0210*/ THE SERVICE IS NOT TO CODE. THE FOLLOWING NEED CHANGE/CORRECTION: 1) PER TEP SERVICE MANUAL, THE RISER CONDUIT MINIMUM SIZE IS 2". 2) A PERMANENT ADDRESS, USING METAL EMBOSSED STRIP OR METALLIC NUMBERS, MUST BE INSTALLED BELOW THE METER. DO NOT USE PENCIL, PEN OR MAGIC MARKER. 3) THE GROUND WIRE MUST BE RUN UNSPLICED FROM ROD TO ROD TO PANEL NEUTRAL. 4) THE GAS PIPING AND COLD WATER PIPING MUST ALSO BE GROUNDED TO PANEL NEUTRAL. 5) MARK THE CIRCUIT BREAKERS/PANEL INDEX. CORRECT AND RECALL. |