Permit: T03EL01233

Parcel: 107132530


Addresses:

456 E KELSO ST


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL01233

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
08/22/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*/ THE SERVICE IS NOT TO CODE. THE FOLLOWING NEED CHANGE/CORRECTION: 1) PER TEP SERVICE MANUAL, THE RISER CONDUIT MINIMUM SIZE IS 2". 2) A PERMANENT ADDRESS, USING METAL EMBOSSED STRIP OR METALLIC NUMBERS, MUST BE INSTALLED BELOW THE METER. DO NOT USE PENCIL, PEN OR MAGIC MARKER. 3) THE GROUND WIRE MUST BE RUN UNSPLICED FROM ROD TO ROD TO PANEL NEUTRAL. 4) THE GAS PIPING AND COLD WATER PIPING MUST ALSO BE GROUNDED TO PANEL NEUTRAL. 5) MARK THE CIRCUIT BREAKERS/PANEL INDEX. CORRECT AND RECALL.