Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
6734 S MISSIONDALE RD
Apply Date:
04/02/2003
Applicant:
PENUELAS INC
Description:
ELECTRIC:INCREASE TO 100 AMPS
Contractors:
  • PENUELAS INC

Permit Reviews

Permit Number - T03EL00636
Permit Status: Final
Permit Description: ELECTRIC:INCREASE TO 100 AMPS
Start Date Submittal Complete Date Status  
04/02/2003 ELECTRICAL 04/02/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03EL00636
Permit Status: Final
Permit Description: ELECTRIC:INCREASE TO 100 AMPS
Total Outstanding Activity Conditions - 1
Date Name
04/02/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T03EL00636
Permit Description: ELECTRIC:INCREASE TO 100 AMPS
Total Completed Inspections - 4
Date Description Inspector Results Comments
04/14/2003 PERMIT FINALED DSANTACR Approved
04/14/2003 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0000*
1.) SERVICE RELOCATION OK, HOWEVER, GROUNDING ELECTRODE CONDUCTOR RUN TO GROUND RODS ON OTHER SIDE OF HOUSE THRU ATTIC SPACE NOT APPROVED. RUN #4 BARE OUTSIDE OF DWELLING.
2.) 1" CONNECTOR NOT INSTALLED PROPERLY ON PANEL.
3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE USING SCREWS OR RIVITS.
4.) WHERE DID YOU SPLICE WIRES IN ATTIC?
5.) BREAKER BLANKS HELD ON WITH TAPE NOT APP.
04/14/2003 ELECTRIC - SERVICE UPGRADE DSANTACR Approved IVRS - Inspection 0000*SENT TO TEP 4/14/03 OK TO CLEAR OK TO CLEAR/OK CABLE DROP.
04/14/2003 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None DOCUMENTS VIEW