Permit: T03EL00636

Parcel: 13815019B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
1.) SERVICE RELOCATION OK, HOWEVER, GROUNDING ELECTRODE CONDUCTOR RUN TO GROUND RODS ON OTHER SIDE OF HOUSE THRU ATTIC SPACE NOT APPROVED. RUN #4 BARE OUTSIDE OF DWELLING.
2.) 1" CONNECTOR NOT INSTALLED PROPERLY ON PANEL.
3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE USING SCREWS OR RIVITS.
4.) WHERE DID YOU SPLICE WIRES IN ATTIC?
5.) BREAKER BLANKS HELD ON WITH TAPE NOT APP.
04/11/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
04/09/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
04/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*LOCATION OF SERVICE IN VIOLATION OF DEDICATED WORKING CLEARANCE. NEED 36" CLEAR SPACE IN FRONT. TO CLOSE TO BLOCK WALL. SEE ART 110-26. NEC.