Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* 1.) SERVICE RELOCATION OK, HOWEVER, GROUNDING ELECTRODE CONDUCTOR RUN TO GROUND RODS ON OTHER SIDE OF HOUSE THRU ATTIC SPACE NOT APPROVED. RUN #4 BARE OUTSIDE OF DWELLING. 2.) 1" CONNECTOR NOT INSTALLED PROPERLY ON PANEL. 3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE USING SCREWS OR RIVITS. 4.) WHERE DID YOU SPLICE WIRES IN ATTIC? 5.) BREAKER BLANKS HELD ON WITH TAPE NOT APP. |
|
| 04/11/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* | |
| 04/09/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 04/04/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*LOCATION OF SERVICE IN VIOLATION OF DEDICATED WORKING CLEARANCE. NEED 36" CLEAR SPACE IN FRONT. TO CLOSE TO BLOCK WALL. SEE ART 110-26. NEC. |