Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
33 W CONGRESS ST
Apply Date:
06/04/2003
Applicant:
N/A
Description:
TI:OFFICE
Contractors:
  • CAYLOR CONSTRUCTION COMPANY , RO

Permit Reviews

Permit Number - T03CM02731
Permit Status: Expired
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
06/04/2003 COMMERCIAL TI 07/02/2003 COMPLETED Review Details
11/05/2003 REVISION 12/02/2003 COMPLETED Review Details
12/17/2003 REVISION - 2ND 01/22/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM02731
Permit Status: Expired
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
06/04/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03CM02731
Permite Description: TI:OFFICE
Total Outstanding Inspections - 17
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE RELOCATION N/A Not Inspected
ELECTRIC - PROGRESS N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
FIRE SPKLR - FINAL N/A Not Inspected
FIRE - FINAL N/A Not Inspected
ENGINEERING - FINAL N/A Not Inspected
LANDSCAPE - FINAL N/A Not Inspected
SIGN - FINAL N/A Not Inspected
NPPO - FINAL N/A Not Inspected
RIGHT OF WAY - FINAL N/A Not Inspected
03/09/2004 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection 0000*
05/20/2004 SHEET ROCK NAILING N/A Cancelled IVRS - Ri canceled
05/24/2004 ELECTRIC - ABOVE CEILING N/A Not ready for Inspection IVRS - Inspection :*
05/24/2004 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*/ 1) SERVICE CONDUITS TO BE AS PER 230-6. 2) JUNCTION/PULL BOX TO BE SEALED ON PRIMARY SIDE. 3) PLANS CALL FOR 1200 AMP SWITCH - WE HAVE 2000 AMP. PLEASE REVISE PLANS. 4) PLEASE PROVIDE LETTER VERIFYING TORQUE OF EQUIPMENT CONNECTIONS AND TERMINATIONS. 5) SES TO BE SECURED TO FLOOR. 6) ACCESS OF SERVICE TO BE AS PER 110-26 (C).
07/21/2003 PLUMBING - ABOVE CEILING N/A Partial Approval IVRS - Inspection 0000*
1) ABS DWV UNDER FLOOR TO TIE IN AT EXISTING OK
2) WATER TEST TO 10 FEET OK
3) COPPER OK
4) OK TO COVER WALLS
5) NEED TO SEE VENT TIE IN AND CLOSET HANGERS
08/06/2003 FRAMING N/A Partial Approval IVRS - Inspection 0000* PENDING OTHER TRADES APPROVAL
08/18/2003 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection 0000*/ BATHROOMS AND PHONE ROOM.

Completed Inspections

Permit Status: Expired
Permit Number: T03CM02731
Permit Description: TI:OFFICE
Total Completed Inspections - 3
Date Description Inspector Results Comments
07/21/2003 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection 0000*
07/21/2003 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection 0000*
06/17/2004 TEP CLEARANCE - AM JKOZUCH Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW