Inspection History: ELECTRIC - FINAL

Permit Number - T03CM02731

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
05/24/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SERVICE CONDUITS TO BE AS PER 230-6. 2) JUNCTION/PULL BOX TO BE SEALED ON PRIMARY SIDE. 3) PLANS CALL FOR 1200 AMP SWITCH - WE HAVE 2000 AMP. PLEASE REVISE PLANS. 4) PLEASE PROVIDE LETTER VERIFYING TORQUE OF EQUIPMENT CONNECTIONS AND TERMINATIONS. 5) SES TO BE SECURED TO FLOOR. 6) ACCESS OF SERVICE TO BE AS PER 110-26 (C).