Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM02731
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) SERVICE CONDUITS TO BE AS PER 230-6. 2) JUNCTION/PULL BOX TO BE SEALED ON PRIMARY SIDE. 3) PLANS CALL FOR 1200 AMP SWITCH - WE HAVE 2000 AMP. PLEASE REVISE PLANS. 4) PLEASE PROVIDE LETTER VERIFYING TORQUE OF EQUIPMENT CONNECTIONS AND TERMINATIONS. 5) SES TO BE SECURED TO FLOOR. 6) ACCESS OF SERVICE TO BE AS PER 110-26 (C). |