Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address NEW:
4635 E BROADWAY BL
Apply Date:
03/19/2003
Applicant:
S A R T D CONSTRUCTION ,
Description:
REMODEL:FACADE
Contractors:
  • S A R T D CONSTRUCTION ,

Permit Reviews

Permit Number - T03CM01361
Permit Status: Expired
Permit Description: REMODEL:FACADE
Start Date Submittal Complete Date Status  
03/19/2003 COMMERCIAL TI 06/09/2003 COMPLETED Review Details
12/24/2003 REVISION 12/24/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM01361
Permit Status: Expired
Permit Description: REMODEL:FACADE
Total Outstanding Activity Conditions - 1
Date Name
03/19/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03CM01361
Permite Description: REMODEL:FACADE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
11/18/2003 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection 0000* NEED STRAPS, POST TO BEAM. GET SPEC INSP. BLDG INSP TO BE LAST INSP.
11/18/2003 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*/ 1) SUPPORT M/C CABLE AS PER CODE WITHIN 12" AND EVERY 6' 2) WE HAVE A SMASHED CABLE ARMOR AND POSSIBLE DAMAGE TO CONDUCTORS, ALSO BROKEN ARMOR 3) USE A SINGEL CABLE CONNECTOR FOR SINGLE ENTRANCES 4) MISSING SCREWS IN RLM FIXTURE 5) WHAT IS EXPOSED NM CONDUCTORS FOR ? 6) INSTALL CABLE INTO FITTINGS AND FITTINGS INTO BOX 7) WILL JUNCTION BOX BE ACCESSIBLE 8) TIGHTEN LOOSE FITTINGS 9) GROUND JUNCTION BOX 10) FILL UNUSED OPENING TO COMBUSTIBLE 11) HAVE EXTRA RIGHTS AND RECEPTACLES ADDED TO PLANS AND REAPPROVED 12) WHERE IS SIGN AS PER PLANS

Completed Inspections

Permit Status: Expired
Permit Number: T03CM01361
Permit Description: REMODEL:FACADE
Total Completed Inspections - 5
Date Description Inspector Results Comments
07/09/2003 EXCAVATION/LAYOUT REBAR & ZON RSUBA Approved IVRS - Inspection 0000*
07/16/2003 ROOF NAILING RSUBA Approved IVRS - Inspection 0000*
11/18/2003 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection 0999*
11/18/2003 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection 0999*
11/18/2003 FRAMING AMATHIES Approved IVRS - Inspection 0999*