Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01361
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) SUPPORT M/C CABLE AS PER CODE WITHIN 12" AND EVERY 6' 2) WE HAVE A SMASHED CABLE ARMOR AND POSSIBLE DAMAGE TO CONDUCTORS, ALSO BROKEN ARMOR 3) USE A SINGEL CABLE CONNECTOR FOR SINGLE ENTRANCES 4) MISSING SCREWS IN RLM FIXTURE 5) WHAT IS EXPOSED NM CONDUCTORS FOR ? 6) INSTALL CABLE INTO FITTINGS AND FITTINGS INTO BOX 7) WILL JUNCTION BOX BE ACCESSIBLE 8) TIGHTEN LOOSE FITTINGS 9) GROUND JUNCTION BOX 10) FILL UNUSED OPENING TO COMBUSTIBLE 11) HAVE EXTRA RIGHTS AND RECEPTACLES ADDED TO PLANS AND REAPPROVED 12) WHERE IS SIGN AS PER PLANS |