Permit: T03CM00023
Permit Details
Apply Date:
01/03/2003
Applicant:
ANDRE GRIER
Description:
INSTALL:GAS SPACE HEATER
Permit Reviews
Permit Number - T03CM00023
Permit Status: Expired
Permit Description: INSTALL:GAS SPACE HEATER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/03/2003 | OTHER | 01/03/2003 | COMPLETED |
| 01/16/2003 | REVISION | 01/16/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03CM00023
Permit Status: Expired
Permit Description: INSTALL:GAS SPACE HEATER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/03/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03CM00023
Permite Description: INSTALL:GAS SPACE HEATER
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PLUMBING - GAS PRESSURE TEST | N/A | Not Inspected | ||
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| 01/13/2003 | PLUMBING - INTERMEDIATE | N/A | Denied | IVRS - Inspection 0999*/ 1) FURNACE "B" VENT IS INSTALLED UPSIDE DOWN IMPROPER DRAW 2) 1" CLEARANCE REQUIRED TO COMBUSTIBLE ROOF SHEATHING FROM FURNACE "B" VENT 3) GROUND UNION NOT ALLOWED EXCEPT AT METER OR APPLIANCE-REPLACE WITH A LEFT AND RIGHT HANDED NIPPLE AND COUPLING 4) GAS LINE IS UNDERSIZED. PROVIDE A CITY OF TUCSON APPROVED GAS SIZE PLAN FOR WHOLE SYSTEM 5) PROVIDE A MINIMUM 10 PSI GAS PRESSURE TEST ON WHOLE GAS SYSTEM |