Inspection Status: Denied
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/13/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) FURNACE "B" VENT IS INSTALLED UPSIDE DOWN IMPROPER DRAW 2) 1" CLEARANCE REQUIRED TO COMBUSTIBLE ROOF SHEATHING FROM FURNACE "B" VENT 3) GROUND UNION NOT ALLOWED EXCEPT AT METER OR APPLIANCE-REPLACE WITH A LEFT AND RIGHT HANDED NIPPLE AND COUPLING 4) GAS LINE IS UNDERSIZED. PROVIDE A CITY OF TUCSON APPROVED GAS SIZE PLAN FOR WHOLE SYSTEM 5) PROVIDE A MINIMUM 10 PSI GAS PRESSURE TEST ON WHOLE GAS SYSTEM |
| 01/10/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ANSWER AT DOOR |