Permit: T02PL00545
Permit Details
Apply Date:
03/04/2002
Applicant:
WRIGHT PLUMBING & HEATING''T''
Description:
GAS LINE:REPLACE
Contractors:
- WRIGHT PLUMBING & HEATING''T''
Outstanding Activity Conditions
Permit Number - T02PL00545
Permit Status: Final
Permit Description: GAS LINE:REPLACE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/04/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02PL00545
Permit Description: GAS LINE:REPLACE
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2002 | PERMIT FINALED | TRINIVJR | Approved | |
| 03/07/2002 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection 0000*GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) PRE SET PRESSURE VALVE @ 125 PSI IS OK 5.) OK TO BACKFILL TRENCH. |
| 03/07/2002 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection 0999* 1.) CAN NOT RUN GAS LINE UNDERGROUND UNDER A PORCH. THE PORCH IS CONSIDERED BY THE UPC AS PART OF THE STRUCTURE SEE SECTION:1211.3 94 UPC. 2.) CAN NOT LONGER RUN P & T DRAIN UP THROUGH ROOF. CITY OF TUCSON WILL ACCEPT THIS ALTERNATE METHOD OF P & T DRAIN INSTALLATION. A.) WATER HTR MUST HAVE DRAIN PAN AND PLUG THE DRAIN OUTLET. B.) EXTEND P & T DRAIN WITH 1" AIR GAP ABOVE PAN. C.) INSTALLA PRESET PRESSURE RELIFE VALVE @ 125 PSI @ A EXTERIOR LOCATION ON COLD SUPPLY. POINT DRAIN OUTLET DOWN AND TEAT IT LIKE A P & T DRAIN. 3.) RE TEST SYSTEM. |