Permit: T02PL00545

Parcel: 12707040A


Addresses:

5162 E 8TH ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/07/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1.) CAN NOT RUN GAS LINE UNDERGROUND UNDER A PORCH. THE PORCH IS CONSIDERED BY THE UPC AS PART OF THE STRUCTURE SEE SECTION:1211.3 94 UPC. 2.) CAN NOT LONGER RUN P & T DRAIN UP THROUGH ROOF. CITY OF TUCSON WILL ACCEPT THIS ALTERNATE METHOD OF P & T DRAIN INSTALLATION. A.) WATER HTR MUST HAVE DRAIN PAN AND PLUG THE DRAIN OUTLET. B.) EXTEND P & T DRAIN WITH 1" AIR GAP ABOVE PAN. C.) INSTALLA PRESET PRESSURE RELIFE VALVE @ 125 PSI @ A EXTERIOR LOCATION ON COLD SUPPLY. POINT DRAIN OUTLET DOWN AND TEAT IT LIKE A P & T DRAIN. 3.) RE TEST SYSTEM.
03/07/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) PRE SET PRESSURE VALVE @ 125 PSI IS OK 5.) OK TO BACKFILL TRENCH.