Permit: T02ME00703
Permit Details
Apply Date:
10/23/2002
Applicant:
D AND H AIR CONDITIONING CO,*C
Description:
REPLACE:FURNACE:A/C UNIT (APA)
Contractors:
- D AND H AIR CONDITIONING CO,*C
Outstanding Activity Conditions
Permit Number - T02ME00703
Permit Status: Final
Permit Description: REPLACE:FURNACE:A/C UNIT (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/23/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02ME00703
Permit Description: REPLACE:FURNACE:A/C UNIT (APA)
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2002 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0999* 1.) AIR HANDLER MUST HAVE MEANS OF DISCONNECTING POWER WITHIN SIGHT OF EQUIPMENT. 2.) MARK UNIT DATA PLATE WITH PROPER HEAT KIT INSTALLED & PROVIDE NECESSARY FUSES. 3.) INSULATION ON REFER LINES IS COMING LOOSE. REPAIR AS NEEDED. 4.) CIRCUIT BREAKER FOR AIR HANDLER IS 100 AMP. CONDENSOR ON ROOF IS OK. |
| 01/17/2003 | PERMIT FINALED | JMILITEL | Approved |