Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. | |
| 11/18/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) AIR HANDLER MUST HAVE MEANS OF DISCONNECTING POWER WITHIN SIGHT OF EQUIPMENT. 2.) MARK UNIT DATA PLATE WITH PROPER HEAT KIT INSTALLED & PROVIDE NECESSARY FUSES. 3.) INSULATION ON REFER LINES IS COMING LOOSE. REPAIR AS NEEDED. 4.) CIRCUIT BREAKER FOR AIR HANDLER IS 100 AMP. CONDENSOR ON ROOF IS OK. |