Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T02ME00390
Permit Details
Apply Date:
06/26/2002
Applicant:
EFFICIENT AIR CONDITIONING,*C,*P
Description:
AIR COND (2) W/HEAT (APA) DOUBLE FEE
Contractors:
- EFFICIENT AIR CONDITIONING,*C,*P
Outstanding Activity Conditions
Permit Number - T02ME00390
Permit Status: Final
Permit Description: AIR COND (2) W/HEAT (APA) DOUBLE FEE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/26/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02ME00390
Permit Description: AIR COND (2) W/HEAT (APA) DOUBLE FEE
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2002 | PERMIT FINALED | JMILITEL | Approved | |
07/12/2002 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0000*1.) OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT. SEE MANUFACTURES RECOMMENDATION. 2.) GAS FLEX EXEEDS MAX. ALLOWABLE LENGTH OF 3' 3.) ELEC. DISCONNECT IS BLOCKING THE UNIT DATA PLATE 4.) LABEL UNIT W/THE ADDRESS. |