Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT. SEE MANUFACTURES RECOMMENDATION. 2.) GAS FLEX EXEEDS MAX. ALLOWABLE LENGTH OF 3' 3.) ELEC. DISCONNECT IS BLOCKING THE UNIT DATA PLATE 4.) LABEL UNIT W/THE ADDRESS. |
| 07/11/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |