Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02ME00390
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*1.) OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT. SEE MANUFACTURES RECOMMENDATION. 2.) GAS FLEX EXEEDS MAX. ALLOWABLE LENGTH OF 3' 3.) ELEC. DISCONNECT IS BLOCKING THE UNIT DATA PLATE 4.) LABEL UNIT W/THE ADDRESS. | |
07/11/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* |