Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Address:
7049 E LUANA DR
Address NEW:
7049 E LUANA DR
Apply Date:
12/11/2002
Applicant:
ARTHUR RODRIGUEZ
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP

Permit Reviews

Permit Number - T02EL02408
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Start Date Submittal Complete Date Status  
12/11/2002 ELECTRICAL 12/11/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02EL02408
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
Date Name
12/11/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T02EL02408
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/18/2002 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection 0245*
12/18/2002 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*1.) CONDUIT CONNECTOR USED FOR LB TERMINATION IN SIDE OF PANEL NOT AN APPROVED METHOD. USE CLOSE NIPPLE WITH SEALING LOCKNUTS.
2.) USE SEALING LOCKNUT ON 1/2 & 3/4 CONNECTOR BELOW LB.
3.) 6/3 ROMEX CANNOT BE RUN EXPOSED TO SPA.
4.) MUST HAVE 2 GROUND RODS INSTALLED 6' OR MORE MIN DISTANCE APART.
5.) BOND WATER & GAS PIPING.
6.) MUST HAVE PERMANENT ADDRESS LABEL, SCREWED OR RIVITED TO PANEL ENCLOSURE.

Documents

File Name Document Type  
None DOCUMENTS VIEW