Permit: T02EL02408
Permit Details
Apply Date:
12/11/2002
Applicant:
ARTHUR RODRIGUEZ
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Permit Reviews
Permit Number - T02EL02408
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/11/2002 | ELECTRICAL | 12/11/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL02408
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/11/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T02EL02408
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2002 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0245* |
| 12/18/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*1.) CONDUIT CONNECTOR USED FOR LB TERMINATION IN SIDE OF PANEL NOT AN APPROVED METHOD. USE CLOSE NIPPLE WITH SEALING LOCKNUTS. 2.) USE SEALING LOCKNUT ON 1/2 & 3/4 CONNECTOR BELOW LB. 3.) 6/3 ROMEX CANNOT BE RUN EXPOSED TO SPA. 4.) MUST HAVE 2 GROUND RODS INSTALLED 6' OR MORE MIN DISTANCE APART. 5.) BOND WATER & GAS PIPING. 6.) MUST HAVE PERMANENT ADDRESS LABEL, SCREWED OR RIVITED TO PANEL ENCLOSURE. |