Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) CONDUIT CONNECTOR USED FOR LB TERMINATION IN SIDE OF PANEL NOT AN APPROVED METHOD. USE CLOSE NIPPLE WITH SEALING LOCKNUTS. 2.) USE SEALING LOCKNUT ON 1/2 & 3/4 CONNECTOR BELOW LB. 3.) 6/3 ROMEX CANNOT BE RUN EXPOSED TO SPA. 4.) MUST HAVE 2 GROUND RODS INSTALLED 6' OR MORE MIN DISTANCE APART. 5.) BOND WATER & GAS PIPING. 6.) MUST HAVE PERMANENT ADDRESS LABEL, SCREWED OR RIVITED TO PANEL ENCLOSURE. |