Permit: T02EL02390
Permit Details
Apply Date:
12/10/2002
Applicant:
KENNETH GALLAGHER
Description:
UPGRADE:ELECTRIC 200 AMP TO 220AMP
Permit Reviews
Permit Number - T02EL02390
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 200 AMP TO 220AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/10/2002 | ELECTRICAL | 12/10/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL02390
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 200 AMP TO 220AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/10/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02EL02390
Permit Description: UPGRADE:ELECTRIC 200 AMP TO 220AMP
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2002 | ELECTRIC - SERVICE UPGRADE | MCAPISTR | Approved | IVRS - Inspection 0210* 1.) REMOVE GROUND BAR INSIDE PANEL AND LAND ALL GROUNDS ON NEUTRAL BAR. SEE THAT NEUTRAL BARS ARE BONDED TO BOX. 2.) BOND COLD WATER AND GAS PIPING TO PANEL NEUTRAL/GROUND BAR. 3.) ADD PERMANENT ADDRESS ON PANEL EXTERIOR. USE METAL EMBOSSED STRIP OR STICK-ON METAL NUMBERS. DO NOT USE "MAGIC MARKER", PEN, OR PENCIL. 4.) MOUNTING SCREWS TO SECURE PANEL TO WALL MUST BE MINIMUM 1/4" DIA. 5.) ADD SECOND CLAMP TO RISER PIPE WITHIN 8" OF BOX. 6.) CHECK W/TEP ABOUT METER HEIGHT. SERVICE REQUIREMENTS MANUEL RESTRICTS HEIGHT OF METER TO 6' 3" TO CENTER FROM GRADE LEVEL. THANKS. |
| 01/07/2003 | PERMIT FINALED | RMAJUTA | Approved | |
| 01/07/2003 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0000* |