Permit: T02EL02390

Parcel: 127121720


Addresses:

5744 E HOLMES ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/07/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
12/24/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*
1.) REMOVE GROUND BAR INSIDE PANEL AND LAND ALL GROUNDS ON NEUTRAL BAR. SEE THAT NEUTRAL BARS ARE BONDED TO BOX.
2.) BOND COLD WATER AND GAS PIPING TO PANEL NEUTRAL/GROUND BAR.
3.) ADD PERMANENT ADDRESS ON PANEL EXTERIOR. USE METAL EMBOSSED STRIP OR STICK-ON METAL NUMBERS. DO NOT USE "MAGIC MARKER", PEN, OR PENCIL.
4.) MOUNTING SCREWS TO SECURE PANEL TO WALL MUST BE MINIMUM 1/4" DIA.
5.) ADD SECOND CLAMP TO RISER PIPE WITHIN 8" OF BOX.
6.) CHECK W/TEP ABOUT METER HEIGHT. SERVICE REQUIREMENTS MANUEL RESTRICTS HEIGHT OF METER TO 6' 3" TO CENTER FROM GRADE LEVEL. THANKS.
12/23/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0920*NO ANSWER NO ANSWER AT DOOR. DOG IN BACKYARD.