Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 12/24/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0210* 1.) REMOVE GROUND BAR INSIDE PANEL AND LAND ALL GROUNDS ON NEUTRAL BAR. SEE THAT NEUTRAL BARS ARE BONDED TO BOX. 2.) BOND COLD WATER AND GAS PIPING TO PANEL NEUTRAL/GROUND BAR. 3.) ADD PERMANENT ADDRESS ON PANEL EXTERIOR. USE METAL EMBOSSED STRIP OR STICK-ON METAL NUMBERS. DO NOT USE "MAGIC MARKER", PEN, OR PENCIL. 4.) MOUNTING SCREWS TO SECURE PANEL TO WALL MUST BE MINIMUM 1/4" DIA. 5.) ADD SECOND CLAMP TO RISER PIPE WITHIN 8" OF BOX. 6.) CHECK W/TEP ABOUT METER HEIGHT. SERVICE REQUIREMENTS MANUEL RESTRICTS HEIGHT OF METER TO 6' 3" TO CENTER FROM GRADE LEVEL. THANKS. |
|
| 12/23/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0920*NO ANSWER NO ANSWER AT DOOR. DOG IN BACKYARD. |