Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
4224 E SPEEDWAY BL
Apply Date:
11/27/2002
Applicant:
PALO VERDE ELECTRIC
Description:
ELECTRIC:SERVICE PANEL CHANGE
Contractors:
  • PALO VERDE ELECTRIC INC ,

Permit Reviews

Permit Number - T02EL02319
Permit Status: Expired
Permit Description: ELECTRIC:SERVICE PANEL CHANGE
Start Date Submittal Complete Date Status  
11/27/2002 ELECTRICAL 11/27/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02EL02319
Permit Status: Expired
Permit Description: ELECTRIC:SERVICE PANEL CHANGE
Total Outstanding Activity Conditions - 1
Date Name
11/27/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T02EL02319
Permite Description: ELECTRIC:SERVICE PANEL CHANGE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/05/2002 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*
1.) NEED CONTR. OR TEP. TO BREAK SEAL ON METER ENCLOSURE COVER TO ALLOW COVER REMOVAL FOR INSPECTION.
2.) MC CABLE MUST BE TERMINATED PROPERLY IN PANEL ENCLOSURE USING PROPER, LISTED FITTINGS, PER NEC. ART 300-15,334,110-3.
3.) SUPPORT MC PER ART 334 NEC.
4.) SERVICE LOCATION OR INSTALLATION IN VIOLATION OF DEDICATED WORKING SPACE MUST HAVE 36" IN FRONT BY 30" HORIZONTAL. THIS IS FROM TOP OF ENCLOSURES TO GROUND LEVEL. PER 110-26 NEC.
5.) NO PERMIT ISSUED FOR NEW BRANCH CIRCUITS RUN TO PANEL. OBTAIN PLOT PLAN, FLOOR PLAN, APPROVED DRAWINGS FOR ALL NEW WIRING.