Permit: T02EL02319
Permit Details
Apply Date:
11/27/2002
Applicant:
PALO VERDE ELECTRIC
Description:
ELECTRIC:SERVICE PANEL CHANGE
Contractors:
- PALO VERDE ELECTRIC INC ,
Permit Reviews
Permit Number - T02EL02319
Permit Status: Expired
Permit Description: ELECTRIC:SERVICE PANEL CHANGE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/27/2002 | ELECTRICAL | 11/27/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL02319
Permit Status: Expired
Permit Description: ELECTRIC:SERVICE PANEL CHANGE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/27/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL02319
Permite Description: ELECTRIC:SERVICE PANEL CHANGE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245* 1.) NEED CONTR. OR TEP. TO BREAK SEAL ON METER ENCLOSURE COVER TO ALLOW COVER REMOVAL FOR INSPECTION. 2.) MC CABLE MUST BE TERMINATED PROPERLY IN PANEL ENCLOSURE USING PROPER, LISTED FITTINGS, PER NEC. ART 300-15,334,110-3. 3.) SUPPORT MC PER ART 334 NEC. 4.) SERVICE LOCATION OR INSTALLATION IN VIOLATION OF DEDICATED WORKING SPACE MUST HAVE 36" IN FRONT BY 30" HORIZONTAL. THIS IS FROM TOP OF ENCLOSURES TO GROUND LEVEL. PER 110-26 NEC. 5.) NO PERMIT ISSUED FOR NEW BRANCH CIRCUITS RUN TO PANEL. OBTAIN PLOT PLAN, FLOOR PLAN, APPROVED DRAWINGS FOR ALL NEW WIRING. |