Permit: T02EL02319

Parcel: 126050690


Addresses:

4224 E SPEEDWAY BL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) NEED CONTR. OR TEP. TO BREAK SEAL ON METER ENCLOSURE COVER TO ALLOW COVER REMOVAL FOR INSPECTION.
2.) MC CABLE MUST BE TERMINATED PROPERLY IN PANEL ENCLOSURE USING PROPER, LISTED FITTINGS, PER NEC. ART 300-15,334,110-3.
3.) SUPPORT MC PER ART 334 NEC.
4.) SERVICE LOCATION OR INSTALLATION IN VIOLATION OF DEDICATED WORKING SPACE MUST HAVE 36" IN FRONT BY 30" HORIZONTAL. THIS IS FROM TOP OF ENCLOSURES TO GROUND LEVEL. PER 110-26 NEC.
5.) NO PERMIT ISSUED FOR NEW BRANCH CIRCUITS RUN TO PANEL. OBTAIN PLOT PLAN, FLOOR PLAN, APPROVED DRAWINGS FOR ALL NEW WIRING.
12/02/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
No access, bld, gates locked.