Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T02EL02206
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
109 W PRINCE RD #05
Address NEW:
109 W PRINCE RD #05
Apply Date:
11/12/2002
Applicant:
AC ARTISANS ELECTRICAL CONT *C
Description:
INSTALL:ELECTRIC CIRCUIT
Contractors:
- AC ARTISANS ELECTRICAL CONT *C
Outstanding Activity Conditions
Permit Number - T02EL02206
Permit Status: Final
Permit Description: INSTALL:ELECTRIC CIRCUIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/12/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02EL02206
Permit Description: INSTALL:ELECTRIC CIRCUIT
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2002 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0999* 1.) TIGHTEN SEALTITE FITTINGS AND SUPPORT SEALTITE 2.) USE AN APPROVED AT LB. CHASE NIPPLE NOT APPROVED. 3.) PLEASE CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4.) BREAKER TO BE LISTED FOR USE BY MANFACTURE OF PANEL 5.) THIS IS AN ILLEGAL TAP POWER TO FOR TENANT SERVICE SUB PANEL NOT PARK BOX. 6.) USE AN APPROVED RAINTITE FITTING TO ENTER JUNCTION BOX. |
| 02/18/2003 | PERMIT FINALED | MCAPISTR | Approved |