Permit: T02EL02206

Parcel: 10603145A


Addresses:

109 W PRINCE RD #05


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL02206

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) TIGHTEN SEALTITE FITTINGS AND SUPPORT SEALTITE
2.) USE AN APPROVED AT LB. CHASE NIPPLE NOT APPROVED.
3.) PLEASE CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
4.) BREAKER TO BE LISTED FOR USE BY MANFACTURE OF PANEL
5.) THIS IS AN ILLEGAL TAP POWER TO FOR TENANT SERVICE SUB PANEL NOT PARK BOX.
6.) USE AN APPROVED RAINTITE FITTING TO ENTER JUNCTION BOX.