Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL02206
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/13/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) TIGHTEN SEALTITE FITTINGS AND SUPPORT SEALTITE 2.) USE AN APPROVED AT LB. CHASE NIPPLE NOT APPROVED. 3.) PLEASE CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4.) BREAKER TO BE LISTED FOR USE BY MANFACTURE OF PANEL 5.) THIS IS AN ILLEGAL TAP POWER TO FOR TENANT SERVICE SUB PANEL NOT PARK BOX. 6.) USE AN APPROVED RAINTITE FITTING TO ENTER JUNCTION BOX. |