Permit: T02EL02044
Permit Details
Apply Date:
10/11/2002
Applicant:
BLANKENBAKER ELECTRIC *C
Description:
UPGRADE:ELECTRIC 60-200 AMP (APA)
Contractors:
- BLANKENBAKER ELECTRIC *C
Outstanding Activity Conditions
Permit Number - T02EL02044
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 60-200 AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/11/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02EL02044
Permit Description: UPGRADE:ELECTRIC 60-200 AMP (APA)
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2002 | PERMIT FINALED | DSANTACR | Approved | |
| 10/18/2002 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection 0000*SENT TO TEP ON 10/21/02 AT 9:15AM OK TO CLEAR OK CABLE DROP. SERVICE UP GRADE OK HOWEVER CONTR. TIED EXISTING #12 AWG SUB-PANEL FEEDER INTO NEW 20 AMP CIRCUIT BREAKER. THE EXISTING SUB PANEL INSTALLED. WITH #6. WIRE. SOMEWHERE IN ATTIC SPACE THE #6 FEEDER WIRE IS SPLICED TO #12 WIRE WHICH WOULD NOT WITHSTAND SUB PANEL LOAD. RECOMMEND HOMEOWNER TO HAVE CONTR. MAKE NECESSARY CORRECTIONS NOT ORIGINALLY UNDER SCOPE OF WORK. |