Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 10/21/02 AT 9:15AM OK TO CLEAR OK CABLE DROP. SERVICE UP GRADE OK HOWEVER CONTR. TIED EXISTING #12 AWG SUB-PANEL FEEDER INTO NEW 20 AMP CIRCUIT BREAKER. THE EXISTING SUB PANEL INSTALLED. WITH #6. WIRE. SOMEWHERE IN ATTIC SPACE THE #6 FEEDER WIRE IS SPLICED TO #12 WIRE WHICH WOULD NOT WITHSTAND SUB PANEL LOAD. RECOMMEND HOMEOWNER TO HAVE CONTR. MAKE NECESSARY CORRECTIONS NOT ORIGINALLY UNDER SCOPE OF WORK. |
| 10/14/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NEED TO SEE SUB PANEL WATER AND GAS BOND. |