Permit: T02EL01996
Permit Details
Apply Date:
10/02/2002
Applicant:
WILKOWSKI ELECTRIC ''T''
Description:
REPAIR:ELECTRIC REPLACE EXISTING- STORM DAMAGE
Contractors:
- WILKOWSKI ELECTRIC ''T''
Outstanding Activity Conditions
Permit Number - T02EL01996
Permit Status: Expired
Permit Description: REPAIR:ELECTRIC REPLACE EXISTING- STORM DAMAGE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/02/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL01996
Permite Description: REPAIR:ELECTRIC REPLACE EXISTING- STORM DAMAGE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*1.) CONTR. REPLACED ENTIRE SERVICE, 400 AMP, 3 DIAMETER WAS REPLACED DUE TO STORM DAMAGE. SERVICE ENERGIZED PRIOR TO CLEARANCE FROM CITY. 2.) RISERS (2) TO BE SUPPORTED USING MIN 1/4" BOLTS. 3.) DISCONNECTS 3 & 4 NEED NEUTRAL CONDUCTORS INSTALLED INSTALLED. PER ART 230,250 NEC. 4.) NEED TO INSPECT WIRING IN CT CAN SEALED WITH TEP LOCKING DEVICE. |