Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) CONTR. REPLACED ENTIRE SERVICE, 400 AMP, 3 DIAMETER WAS REPLACED DUE TO STORM DAMAGE. SERVICE ENERGIZED PRIOR TO CLEARANCE FROM CITY. 2.) RISERS (2) TO BE SUPPORTED USING MIN 1/4" BOLTS. 3.) DISCONNECTS 3 & 4 NEED NEUTRAL CONDUCTORS INSTALLED INSTALLED. PER ART 230,250 NEC. 4.) NEED TO INSPECT WIRING IN CT CAN SEALED WITH TEP LOCKING DEVICE. |