Permit: T02EL01996

Parcel: 133290060


Addresses:

8321 E BROADWAY BL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) CONTR. REPLACED ENTIRE SERVICE, 400 AMP, 3 DIAMETER WAS REPLACED DUE TO STORM DAMAGE. SERVICE ENERGIZED PRIOR TO CLEARANCE FROM CITY. 2.) RISERS (2) TO BE SUPPORTED USING MIN 1/4" BOLTS. 3.) DISCONNECTS 3 & 4 NEED NEUTRAL CONDUCTORS INSTALLED INSTALLED. PER ART 230,250 NEC. 4.) NEED TO INSPECT WIRING IN CT CAN SEALED WITH TEP LOCKING DEVICE.