Permit: T02EL01927
Permit Details
Apply Date:
09/24/2002
Applicant:
DIRECT ELECTRICAL SERVICES INC
Description:
UPGRADE:ELECTRIC 50AMP TO 100AMP (APA)
Contractors:
- DIRECT ELECTRICAL SERVICES INC
Outstanding Activity Conditions
Permit Number - T02EL01927
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 50AMP TO 100AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/24/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL01927
Permite Description: UPGRADE:ELECTRIC 50AMP TO 100AMP (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*1.) SECURE BONDING CONDUCTOR TO STRUCTURE BY GAS & WATER 2.) WHERE IS PAPERWORK FOR JOB. 3.) MAINTAIN A LEVEL WORKING PLATFORM OR SURFACE BELOW PANELS. 4.) PLEASE LABEL PANELS ON OUTSIDE COVER 5.) PLEASE TIGHEN GROUND BAR. 6.) 1/4 MININIUM HARDWARE IS NEEDED TO SUPPORT SERVICE EQUIPMENT. 7.) SEAL TOP OF PANEL 8.) BOND BOTH GAS SERVICE. |