Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SECURE BONDING CONDUCTOR TO STRUCTURE BY GAS & WATER 2.) WHERE IS PAPERWORK FOR JOB. 3.) MAINTAIN A LEVEL WORKING PLATFORM OR SURFACE BELOW PANELS. 4.) PLEASE LABEL PANELS ON OUTSIDE COVER 5.) PLEASE TIGHEN GROUND BAR. 6.) 1/4 MININIUM HARDWARE IS NEEDED TO SUPPORT SERVICE EQUIPMENT. 7.) SEAL TOP OF PANEL 8.) BOND BOTH GAS SERVICE. |