Permit: T02EL01914
Permit Details
Apply Date:
09/23/2002
Applicant:
PRESTON ELECTRIC INC
Description:
RELOCATE & UPGRADE ELECTRIC TO 200AMP
Contractors:
- PRESTON ELECTRIC INC
Permit Reviews
Permit Number - T02EL01914
Permit Status: Expired
Permit Description: RELOCATE & UPGRADE ELECTRIC TO 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/23/2002 | ELECTRICAL | 09/23/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL01914
Permit Status: Expired
Permit Description: RELOCATE & UPGRADE ELECTRIC TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/23/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL01914
Permite Description: RELOCATE & UPGRADE ELECTRIC TO 200AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0210*THE 60 AMP CIRCUIT BREAKER FEEDS #8 THHN. # 8 THHN. IS RATED TO 50AMP MAX. 2.) TWENTY AMP (20A) C.B. FEED 15AMP. CIRCUITS ON #14 WINE. 3.) THE J' BOX INSIDE THE WALL MUST BE READILY ACCESSIBLE. THIS IS WHERE THE EXISTING WIRING IS LOCATED AND SPLICED. 4.) BOND THE WATER LINE AND/OR TO GAS PIPING THANKS. |
Completed Inspections
Permit Status: Expired
Permit Number: T02EL01914
Permit Description: RELOCATE & UPGRADE ELECTRIC TO 200AMP
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2002 | ELECTRIC - SERVICE UPGRADE | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 09/26/2002 | ELECTRIC - SERVICE RELOCATION | RMAJUTA | Approved | IVRS - Inspection 0000*OK TO CLEAR SERVICE INCREASE CALL FOR FINAL ONCE CHANGE OVER COMPLETE. 1.) ATTACH WATER BOND. 2.) INSTALL A PERMANENT ADDRESS ON SERVICE. |