Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*THE 60 AMP CIRCUIT BREAKER FEEDS #8 THHN. # 8 THHN. IS RATED TO 50AMP MAX. 2.) TWENTY AMP (20A) C.B. FEED 15AMP. CIRCUITS ON #14 WINE. 3.) THE J' BOX INSIDE THE WALL MUST BE READILY ACCESSIBLE. THIS IS WHERE THE EXISTING WIRING IS LOCATED AND SPLICED. 4.) BOND THE WATER LINE AND/OR TO GAS PIPING THANKS. |
| 09/25/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |