Permit: T02EL01914

Parcel: 130031500


Addresses:

2642 E KESWICK CI

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0210*THE 60 AMP CIRCUIT BREAKER FEEDS #8 THHN. # 8 THHN. IS RATED TO 50AMP MAX. 2.) TWENTY AMP (20A) C.B. FEED 15AMP. CIRCUITS ON #14 WINE. 3.) THE J' BOX INSIDE THE WALL MUST BE READILY ACCESSIBLE. THIS IS WHERE THE EXISTING WIRING IS LOCATED AND SPLICED. 4.) BOND THE WATER LINE AND/OR TO GAS PIPING THANKS.
09/25/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*