Permit: T02EL01685
Permit Details
Apply Date:
08/15/2002
Applicant:
GARCIA FRANCISCO
Description:
UPGRADE:ELECTRIC TO 100 AMP
Outstanding Activity Conditions
Permit Number - T02EL01685
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 100 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/15/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL01685
Permite Description: UPGRADE:ELECTRIC TO 100 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2002 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR SERVICE FOR CHANGE OVER INC. CALL WHEN CHANGE OVER COMPLETED. 1.) ADDRESS SERVICE 2.) ADD 2ND STRAP TO SERVICE. THUR WALL 3.) LOUD CONDUCTORS ON METER PRIMARY. |
| 09/05/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*1.) JUNCTION BOX USED HAS TO BE RAINTIGHT TYPE FOR OUTDOORS ONE USE NOT RAINTIGHT 2.) CONDUIT FITTINGS ALSO HAVE TO BE RAIN TIGHT FOR OUTDOOR USE SET SCREW TYPE NOT RAINTIGHT. 3.) THE WIRES GOING INTO THE HOUSE ARE RATED #12 GAGE THEY NEED TO BE ON A 20AMP CIRCUIT BREAKER NOT 30 AMP. 4.) THE BACK OF THE JUNCTION BOX CANNOT BE CUT OPEN NEED TO PUNCH A HOLE AND INSERT A PLASTIC BUSHING FOR WIRES TO GO THUR. |