Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) JUNCTION BOX USED HAS TO BE RAINTIGHT TYPE FOR OUTDOORS ONE USE NOT RAINTIGHT 2.) CONDUIT FITTINGS ALSO HAVE TO BE RAIN TIGHT FOR OUTDOOR USE SET SCREW TYPE NOT RAINTIGHT. 3.) THE WIRES GOING INTO THE HOUSE ARE RATED #12 GAGE THEY NEED TO BE ON A 20AMP CIRCUIT BREAKER NOT 30 AMP. 4.) THE BACK OF THE JUNCTION BOX CANNOT BE CUT OPEN NEED TO PUNCH A HOLE AND INSERT A PLASTIC BUSHING FOR WIRES TO GO THUR. |