Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T02EL01663
Permit Details
Apply Date:
08/14/2002
Applicant:
METRO PERMIT EXPRESS, INC
Description:
ELECTRIC:UPGRADE
Contractors:
- VALLEY ENERGY CORP ,
Permit Reviews
Permit Number - T02EL01663
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/14/2002 | ELECTRICAL | 08/19/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL01663
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/14/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02EL01663
Permit Description: ELECTRIC:UPGRADE
Total Completed Inspections - 6
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2002 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection 0000*OK 4" PVC THE REST TO TEP TRANSFORMERS. |
12/31/2002 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1/2/03 AT 9:15AM 1.) BOND GUTTER ENCLOUSER 2.) PLEASE PROVIDE REJECTION PINS 3.) SIZE GROUNDING EQUIPMENT CONDUCTORS TO 250-122. 4.) PLEASE LABEL SERVICE DISCONNECTS 5.) PLEASE IDENTIFY BUILING NUMBERS AS PER BUILDING CODES. 6.) NEUTRAL TO BE BONDED TO GROUNDING ELECTRODE CONDUCTOR AT GUTTER #2. OK TO RELEASE POWER PLEASE RECALL BY 1-2-03. |
12/31/2002 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection 0000* |
02/19/2003 | PERMIT FINALED | MCAPISTR | Approved | |
02/19/2003 | ELECTRIC - CABLE DROP | MCAPISTR | Approved | |
02/19/2003 | ELECTRIC - UFER | MCAPISTR | Approved |