Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/23/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*THE FOLLOWING ROOMS HAVE BEEN COMPLETED 9,10,11, PNL F. AND RMS 19 & 20 PNL E. | |
| 12/31/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 1/2/03 AT 9:15AM 1.) BOND GUTTER ENCLOUSER 2.) PLEASE PROVIDE REJECTION PINS 3.) SIZE GROUNDING EQUIPMENT CONDUCTORS TO 250-122. 4.) PLEASE LABEL SERVICE DISCONNECTS 5.) PLEASE IDENTIFY BUILING NUMBERS AS PER BUILDING CODES. 6.) NEUTRAL TO BE BONDED TO GROUNDING ELECTRODE CONDUCTOR AT GUTTER #2. OK TO RELEASE POWER PLEASE RECALL BY 1-2-03. |