Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
765 W CALLE LERDO
Apply Date:
05/13/2002
Applicant:
ARNOLD PAREDEZ
Description:
UPGRADE:ELECTRIC 60AMP TO 100AMP
Contractors:
  • DESERT SUN ELECTRIC L L C

Outstanding Activity Conditions

Permit Number - T02EL01003
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Activity Conditions - 1
Date Name
05/13/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T02EL01003
Permite Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE UPGRADE N/A Not Inspected
05/17/2002 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*1.) ONCE A SERVICE IS UPGRADE IT MUST COMPLY TO CURRENT CODE ITS REQUIRED THAT THE SPACE BELOW THE PANEL AND 3' OUT BE A CLEAR DEDICATED SPACE 110-26 99NEC THE WATER LINE BELOW SERVICE ISIN THAT SPACE. 2.)CANNOT RUN THE GROUND WIRE ACCROSS SLAB POSSES AT TRIP HAZARDS RUN IT OVER UP TO UNDER PORCH AND DOWN 4X4 AND STAPLE IT, RUN GROUND RODS FLUSH TO GRADE OR BELOW. 3.) RESUPPORT OLD SE CABLE TO STRUCTURE.