Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/17/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) ONCE A SERVICE IS UPGRADE IT MUST COMPLY TO CURRENT CODE ITS REQUIRED THAT THE SPACE BELOW THE PANEL AND 3' OUT BE A CLEAR DEDICATED SPACE 110-26 99NEC THE WATER LINE BELOW SERVICE ISIN THAT SPACE. 2.)CANNOT RUN THE GROUND WIRE ACCROSS SLAB POSSES AT TRIP HAZARDS RUN IT OVER UP TO UNDER PORCH AND DOWN 4X4 AND STAPLE IT, RUN GROUND RODS FLUSH TO GRADE OR BELOW. 3.) RESUPPORT OLD SE CABLE TO STRUCTURE. |