Permit: T02EL00764
Permit Details
Apply Date:
04/15/2002
Applicant:
N/A
Description:
UPGRADE: 200AMP
Contractors:
- VAUGHN S ELECTRIC ACC ,
- VAUGHN S ELECTRIC ACC, *C
Permit Reviews
Permit Number - T02EL00764
Permit Status: Final
Permit Description: UPGRADE: 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/15/2002 | ELECTRICAL | 10/17/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL00764
Permit Status: Final
Permit Description: UPGRADE: 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/15/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T02EL00764
Permit Description: UPGRADE: 200AMP
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2002 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection 0920*NO ACCESS,GATE LOCKED. |
| 11/08/2002 | ELECTRIC - SERVICE UPGRADE | RSUBA | Approved | IVRS - Inspection 0000*1.) USE ANTI-OXIDATION PASTE GENEROUSLY SO I CAN TELL THAT YOU USED IT. 2.) NEED ACCESS TO PANEL A & B BOTH SHOULD HAVE MAIN BREAKERS & GROUNDING ELECTRODE SYSTEM. & H20 BOND ETC. 3.) RECEPT S/B GFI PROTECTED. 4.) DRIVE RODS FLUSH OR BELOW GRADE. THANKS. |
| 01/22/2003 | PERMIT FINALED | RHOLLAND | Approved |