Permit: T02EL00764

Parcel: 11450003B


Addresses:

8289 E WOODLAND RD

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/22/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP ON 1/24/03 AT 9:15AM 1.) A MANUFACTURS HOLD DOWN IS NEEDED FOR BACK FEED BREAKERS
2.) THERE IS NO GROUNDING ELECTRODE SYSTEM ON THE EXISTING HOUSES AT THIS TIME. OK TO CLEAR.
11/08/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) USE ANTI-OXIDATION PASTE GENEROUSLY SO I CAN TELL THAT YOU USED IT. 2.) NEED ACCESS TO PANEL A & B BOTH SHOULD HAVE MAIN BREAKERS & GROUNDING ELECTRODE SYSTEM. & H20 BOND ETC. 3.) RECEPT S/B GFI PROTECTED. 4.) DRIVE RODS FLUSH OR BELOW GRADE. THANKS.
11/06/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
11/04/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0920*GATE LOCKED!! DONT KNOW THE COMBO #FOR THE OTHER ELECTRIC GATE.