Permit: T02EL00620
Permit Details
Apply Date:
03/25/2002
Applicant:
PUEBLO ELECTRIC SERVICES ''T''
Description:
UPGRADE:ELECTRIC (APA)
Contractors:
- PUEBLO ELECTRIC SERVICES ''T''
Outstanding Activity Conditions
Permit Number - T02EL00620
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/25/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T02EL00620
Permite Description: UPGRADE:ELECTRIC (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2002 | ELECTRIC - FINAL | N/A | Denied | CORRECTIONS REQUIRED: 1.) THE GROUND RODS ARE TO BE CONNECTED IN SERIES 6'4 SO THAT THEY PROVIDE COLLECTIVELY A 25 OHM OR LESS PATH TO GROUND AT ALL TIMES. 2.) THE SERVICE RISER MUST HAVE AT LEAST TWO (2) CLAMPS. 3.) CORRECT THE GROUND CLAMP, ON ANY PIPE, ON A CLEAN RUST FREE SURFACE. 4.) BUILDING STEEL AND GAS PIPING MUST ALSO BE BONDED TO THE SERVICE. 5.)SUBMIT A FULL SET OF PLANS/ DRAWINGS FOR THE SERVICES AND EACH OF THE THREE (3) OCCUPANCIES BEING SERVED. 6.) THIS PERMIT WILL HAVE TO BE EXPANDED TO INCORPORATE THE THREE METERS (3PAK) BEING INSTALLED. CITY OF TUCSON PLANNING DEPARTMENT. REVIEW MUST BE INCLUDED. THERE MUST BE THREE SEPARATE ADDRESS. LABEL EACH METER. |