Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/10/2002 |
ELECTRIC - FINAL |
|
Denied |
CORRECTIONS REQUIRED: 1.) THE GROUND RODS ARE TO BE CONNECTED IN SERIES 6'4 SO THAT THEY PROVIDE COLLECTIVELY A 25 OHM OR LESS PATH TO GROUND AT ALL TIMES. 2.) THE SERVICE RISER MUST HAVE AT LEAST TWO (2) CLAMPS. 3.) CORRECT THE GROUND CLAMP, ON ANY PIPE, ON A CLEAN RUST FREE SURFACE. 4.) BUILDING STEEL AND GAS PIPING MUST ALSO BE BONDED TO THE SERVICE. 5.)SUBMIT A FULL SET OF PLANS/ DRAWINGS FOR THE SERVICES AND EACH OF THE THREE (3) OCCUPANCIES BEING SERVED. 6.) THIS PERMIT WILL HAVE TO BE EXPANDED TO INCORPORATE THE THREE METERS (3PAK) BEING INSTALLED. CITY OF TUCSON PLANNING DEPARTMENT. REVIEW MUST BE INCLUDED. THERE MUST BE THREE SEPARATE ADDRESS. LABEL EACH METER. |