Permit: T02EL00553
Permit Details
Apply Date:
03/18/2002
Applicant:
HECTOR OLIVAS
Description:
UPGRADE:ELECTRIC & REPLACE:RISER
Permit Reviews
Permit Number - T02EL00553
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC & REPLACE:RISER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/18/2002 | ELECTRICAL | 03/18/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL00553
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC & REPLACE:RISER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/18/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL00553
Permite Description: UPGRADE:ELECTRIC & REPLACE:RISER
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2002 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0245*NOTES 1.) INSTALL LISTED HUB FOR RISER ATTACHMENT 110-3NEC. 2.) INSTALL STRAP TO SUPPORT RISER WITH IN 3' OF CABINATE. 3.) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE.4.) #10 BARE COPPER FOR GROUND ELECTRODE TO SMALL, USE #4. 5.) GROUND RODS HAVE TO BE MIN 8' LONG. |
| 07/03/2002 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection 0000* |