Permit: T02EL00553

Parcel: 138201170


Addresses:

6942 S LEARY DR

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/02/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*NOTES 1.) INSTALL LISTED HUB FOR RISER ATTACHMENT 110-3NEC. 2.) INSTALL STRAP TO SUPPORT RISER WITH IN 3' OF CABINATE. 3.) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE.4.) #10 BARE COPPER FOR GROUND ELECTRODE TO SMALL, USE #4. 5.) GROUND RODS HAVE TO BE MIN 8' LONG.