Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL LISTED HUB FOR RISER ATTACHMENT 110-3NEC. 2.) INSTALL STRAP TO SUPPORT RISER WITH IN 3' OF CABINATE. 3.) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE.4.) #10 BARE COPPER FOR GROUND ELECTRODE TO SMALL, USE #4. 5.) GROUND RODS HAVE TO BE MIN 8' LONG. |