Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address NEW:
2700 E SPEEDWAY BL
Apply Date:
04/19/2002
Applicant:
MECHANICAL MAINTENANCE INC ,
Description:
MECHANICAL & UPGRADE:ELECTRIC
Contractors:
  • MECHANICAL MAINTENANCE INC ,

Permit Reviews

Permit Number - T02CM02037
Permit Status: Closed
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
Start Date Submittal Complete Date Status  
07/02/2002 COMMERCIAL TI 07/18/2002 COMPLETED Review Details
07/25/2003 REVISION 07/25/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM02037
Permit Status: Closed
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
Total Outstanding Activity Conditions - 1
Date Name
04/19/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Closed
Permit Number: T02CM02037
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
Total Completed Inspections - 9
Date Description Inspector Results Comments
09/19/2002 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection 0000*
09/24/2002 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection 0000*OK TO COVER GRID W/TILES SOUTH 1ST. FLR. CLASS ROOMS.
10/04/2002 FRAMING AMATHIES Approved IVRS - Inspection 0000*DUCT CHASE DRYWALL OK OK TO SHEETROCK FRAMING.
10/30/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection 0000*CHECKED FIRE DAMPER OPENINGS 2ND FLOOR. OK TO COMPLETE DAMPERS. PROVIDE REVISION FROM ARCHITED ON DELETED FIRE/SMOKE DAMPER.
11/04/2002 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection 0000*
11/06/2002 SHEET ROCK NAILING AMATHIES Approved IVRS - Inspection 0000*
12/19/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0000*
NOTES OK TO ENERGIZE PANEL "FC" 1ST FLOOR TO RE-ENERGIZE PARKING LOT LIGHTS. PANEL IN AREA DAMAGED BY FIRE. CONTR. DISCONNECTED DAMAGED CKTS, ALEX WITH TANQUE VERDE ELECTRIC.
08/14/2003 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0999*/1) HORIZONTAL SECTIONS OF CONDENSATE DRAIN PIPE ON ROOF DOES NOT HAVE SLOPE. PROVIDE MIN. 1/8" PER FT. ADD ANOTHER BLOCK WHERE MISSING. PAINT W/ LATEX PAINT. 2) PERMANENTLY LABEL ALL EQUIPMENT W/UNIT NUMBER OR AREA BEING SERVED. LABEL FAN COILS ALSO. MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED AND FUSE UNITS ACCORDINGLY. DO NOT USE INK TO LABEL OUTDOOR EQUIPMENT. 3) SECURE VERTICAL SECTION OF PVC AT PLAY AREA. 4) EQUIPMENT WITHIN 10' TO THE EDGE OF THE ROOF MUST HAVE A GUARD RAIL. SEE SEC. 304.9 2000 IMC. 5) FIRE DAMPER MISSING AT LOBBY CORRIDOR.
01/31/2008 BUILDING - FINAL LHANLY Approved REFERENCE T03CM00454

Documents