Permit: T02CM02037
Permit Details
Apply Date:
04/19/2002
Applicant:
MECHANICAL MAINTENANCE INC ,
Description:
MECHANICAL & UPGRADE:ELECTRIC
Contractors:
- MECHANICAL MAINTENANCE INC ,
Permit Reviews
Permit Number - T02CM02037
Permit Status: Closed
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/02/2002 | COMMERCIAL TI | 07/18/2002 | COMPLETED |
| 07/25/2003 | REVISION | 07/25/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02CM02037
Permit Status: Closed
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/19/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T02CM02037
Permit Description: MECHANICAL & UPGRADE:ELECTRIC
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2002 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection 0000* |
| 09/24/2002 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection 0000*OK TO COVER GRID W/TILES SOUTH 1ST. FLR. CLASS ROOMS. |
| 10/04/2002 | FRAMING | AMATHIES | Approved | IVRS - Inspection 0000*DUCT CHASE DRYWALL OK OK TO SHEETROCK FRAMING. |
| 10/30/2002 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection 0000*CHECKED FIRE DAMPER OPENINGS 2ND FLOOR. OK TO COMPLETE DAMPERS. PROVIDE REVISION FROM ARCHITED ON DELETED FIRE/SMOKE DAMPER. |
| 11/04/2002 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection 0000* |
| 11/06/2002 | SHEET ROCK NAILING | AMATHIES | Approved | IVRS - Inspection 0000* |
| 12/19/2002 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection 0000* NOTES OK TO ENERGIZE PANEL "FC" 1ST FLOOR TO RE-ENERGIZE PARKING LOT LIGHTS. PANEL IN AREA DAMAGED BY FIRE. CONTR. DISCONNECTED DAMAGED CKTS, ALEX WITH TANQUE VERDE ELECTRIC. |
| 08/14/2003 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0999*/1) HORIZONTAL SECTIONS OF CONDENSATE DRAIN PIPE ON ROOF DOES NOT HAVE SLOPE. PROVIDE MIN. 1/8" PER FT. ADD ANOTHER BLOCK WHERE MISSING. PAINT W/ LATEX PAINT. 2) PERMANENTLY LABEL ALL EQUIPMENT W/UNIT NUMBER OR AREA BEING SERVED. LABEL FAN COILS ALSO. MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED AND FUSE UNITS ACCORDINGLY. DO NOT USE INK TO LABEL OUTDOOR EQUIPMENT. 3) SECURE VERTICAL SECTION OF PVC AT PLAY AREA. 4) EQUIPMENT WITHIN 10' TO THE EDGE OF THE ROOF MUST HAVE A GUARD RAIL. SEE SEC. 304.9 2000 IMC. 5) FIRE DAMPER MISSING AT LOBBY CORRIDOR. |
| 01/31/2008 | BUILDING - FINAL | LHANLY | Approved | REFERENCE T03CM00454 |