Permit: T02CM02037

Parcel: 12501001A


Addresses:

2700 E SPEEDWAY BL


Inspection Status: Closed

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM02037

Inspection Description - MECHANICAL - FINAL

Inspection Status - Closed

Date Description Inspector Results Comments
01/31/2008 MECHANICAL - FINAL Closed REFERENCE T03CM00454
08/14/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/1) HORIZONTAL SECTIONS OF CONDENSATE DRAIN PIPE ON ROOF DOES NOT HAVE SLOPE. PROVIDE MIN. 1/8" PER FT. ADD ANOTHER BLOCK WHERE MISSING. PAINT W/ LATEX PAINT. 2) PERMANENTLY LABEL ALL EQUIPMENT W/UNIT NUMBER OR AREA BEING SERVED. LABEL FAN COILS ALSO. MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED AND FUSE UNITS ACCORDINGLY. DO NOT USE INK TO LABEL OUTDOOR EQUIPMENT. 3) SECURE VERTICAL SECTION OF PVC AT PLAY AREA. 4) EQUIPMENT WITHIN 10' TO THE EDGE OF THE ROOF MUST HAVE A GUARD RAIL. SEE SEC. 304.9 2000 IMC. 5) FIRE DAMPER MISSING AT LOBBY CORRIDOR.