Permit Details

Status:
C of o
Type:
SINGLE FAMILY NEW
Address NEW:
1066 N PRESSYC PL
Apply Date:
02/06/2002
Applicant:
LE COCQ CONSTRUCTION COMPANY INC
Description:
TOWNHOUSE:TD#15-04-09
Contractors:
  • LE COCQ CONSTRUCTION COMPANY INC

Permit Reviews

Permit Number - T02CM00646
Permit Status: C of o
Permit Description: TOWNHOUSE:TD#15-04-09
Start Date Submittal Complete Date Status  
02/06/2002 RESIDENTIAL BLDG/ZONING/FLOOD 02/11/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM00646
Permit Status: C of o
Permit Description: TOWNHOUSE:TD#15-04-09
Total Outstanding Activity Conditions - 1
Date Name
02/06/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T02CM00646
Permit Description: TOWNHOUSE:TD#15-04-09
Total Completed Inspections - 25
Date Description Inspector Results Comments
02/25/2002 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection 0000*
02/27/2002 STEM WALL/RETAINING WALL AQUIROZ Approved IVRS - Inspection 0000*
03/05/2002 PLUMBING - ROUGH, SOIL TRINIVJR Approved NOT READY FOR INSPECTION
03/13/2002 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection 0000*PARTIAL WRAP PLUMBING BEFORE POURING CONCRETE.
04/29/2002 ROOF NAILING AQUIROZ Approved IVRS - Inspection 0000*
04/29/2002 EXT METAL CLIPS/EXT SHEATHING AQUIROZ Approved IVRS - Inspection 0000*NEED 2 BOLTS AT COLUMNS.
06/12/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection 0000*OK FOR SHEET ROCK.
06/12/2002 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection 0000*1.) OVERHEAD WATER DISTRIBUTION IS OK 2.) WASTE & VENT SYSTEM IS OK 3.) GAS PRESSURE TEST IS OK 4.) OK FOR DRYWALL.
06/18/2002 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection 0000*THIS APPLIES TO ALL UNITS THE "UFER" GROUND WAS INSTALLED CENTER OF THE SIDE SLIDING GLASS DOOR. NONE OF THE UNITS HAVE A "UFER" AT OR NEAR THE LOAD CENTER. WHAT REMEDY WILL BE TAKEN TO PROVIDE A MADE ELECTRODE UFER GROUND SOURCE FOR EACH OF THE ELEVEN (11) UNITS? REFER TO NEC ART 250 & CITY AMENDMENT.
06/20/2002 FRAMING AMATHIES Approved IVRS - Inspection 0000*
06/20/2002 FRAMING RSUBA Approved IVRS - Inspection 0999*
07/02/2002 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection 0000*FRAMING NOT COMPLETE AT MASTER BEDROOM
07/02/2002 STUCCO MESH AQUIROZ Approved IVRS - Inspection 0000*
07/11/2002 ELECTRIC - CABLE DROP DSANTACR Approved IVRS - Inspection 0000*OK TO CLEAR.
12/12/2002 PLUMBING - YARD WTR LINE/TEST TRINIVJR Approved IVRS - Inspection 0000*OK TO BACKFILL TRENCH.
12/17/2002 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection 0000*1.) PLUMBING FINAL IS OK
2.) OK FOR C OF O.
12/17/2002 PLUMBING - SEWER HCS CONNECT TRINIVJR Approved
12/17/2002 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved
12/24/2002 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection 0000*
12/24/2002 ELECTRIC - TEMPORARY SERVICE MCAPISTR Approved
12/24/2002 ELECTRIC - UFER MCAPISTR Approved
12/30/2002 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0000*
01/02/2003 PERMIT FINALED AQUIROZ Approved
01/02/2003 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection 0000*
01/03/2003 U VALUE FOR WINDOW AQUIROZ Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW
C OF O_08-07-2003.TIF CERT OF OCC VIEW